Carrier furnace status code 34 (ignition proving failure) and code 14 (ignition lockout)
What codes 34 and 14 mean
Carrier's status code list says 34: Ignition proving failure. The control will try three more times before lockout 14 occurs. If the flame signal is lost during the blower on-delay period, the blower comes on for the selected blower-off delay. 14: Ignition lockout auto-resets after three hours.
In plain language: the igniter heated and gas was supplied, but the control could not confirm a flame with the flame sensor, so it shut the gas off for safety.
Carrier's check list for code 34
- Oxide buildup on the flame sensor (the technician document says to clean it with fine steel wool)
- Proper flame-sense microamps: 0.5 microamps DC minimum, 4.0 to 6.0 nominal
- Manual gas valve shut off
- Control ground continuity; the green/yellow wire must be connected to the furnace sheet metal
- Gas valve defective or gas valve turned off
- Low inlet gas pressure
- Inadequate flame carryover or rough ignition
- Defective hot surface igniter
- The flame sensor must not be grounded
What is safe for a homeowner, and what is not
Carrier's consumer page on flame sensors says a dirty or faulty flame sensor is one possible cause when a furnace ignites and then shuts off shortly afterward, and it recommends that a trained HVAC professional clean or replace internal parts like the sensor. Carrier also stresses that a flame sensor is only one possible cause, because ignition, wiring, grounding and gas supply problems can look the same.
The homeowner-level checks are small: make sure the furnace's manual gas shutoff handle is in the open position (handle in line with the pipe) and that other gas appliances work. Do not remove burner or blower doors, test gas pressure or bend or scrape the sensor yourself.
Related symptoms
If your furnace starts, runs for a few seconds and shuts off, see furnace short cycling. If the igniter glows but burners never light, see igniter glows but no flame.
Frequently asked questions
How many times does the furnace try to light before code 14?
Carrier's table says the control will try three more times after the first failed attempt before ignition lockout 14 occurs. Carrier's consumer guidance adds that the number of attempts varies by model, so check your own furnace documentation.
How do I reset code 14?
Carrier says ignition lockout 14 auto-resets after three hours. The service manual describes other reset steps for technicians; if the code keeps returning, have the furnace serviced instead of resetting repeatedly.
Does code 34 mean the igniter is bad?
Not necessarily. A defective hot surface igniter is on the list, but so are the flame sensor, gas supply, gas valve, grounding and ignition carryover. A technician can measure flame-sense microamps to tell the difference.
Sources
- SP05-59 Service and Maintenance Procedures: Deluxe 4-Way Multipoise 2-Stage Direct-Vent Condensing Gas Furnace (Carrier (shareddocs.com)) Covers: Carrier 2-stage condensing gas furnaces with the status-code LED control described in the document. Other Carrier, Bryant and Payne boards can use different codes; check the service label on your furnace.