HeatingCodes

Daikin FTXC mini-split error codes

Daikin wall-mounted units flash a code on the indoor unit and show it on the remote. This is a service manual, so the full troubleshooting flow charts assume a trained technician with meters, but the code list itself tells you which part of the system the unit is complaining about.

What this table coversError codes from section 4.1 of Daikin service manual DAMA-SM-23-020 (FTXC series inverter wall-mounted heat pump, 60 Hz). Rows that the table splits ambiguously are left out.

How to read the display

Codes starting with A or C are indoor unit faults. Codes starting with E, F, H, J, L or P are outdoor unit faults. U codes are system-level (voltage, communication, installation).

The service manual tells technicians to turn the power switch off before connecting or disconnecting connectors, because parts can be damaged. That is one more reason the deeper steps are not for homeowners.

Daikin code table

CodeMeaningWhat the document says
00 Normal condition
U2 Low-voltage detection or over-voltage detection
U4 Signal transmission error (between indoor unit and outdoor unit)
UA Installation error (between indoor unit and outdoor unit)
A1 Indoor unit PCB abnormality
A5 Freeze-up protection control
A6 Indoor fan motor (DC motor) or related abnormality
C4 Indoor heat exchanger thermistor or related abnormality
C9 Room temperature thermistor or related abnormality
E1 Outdoor unit PCB abnormality
E3 Actuation of high pressure switch
E6 Compressor lock
E7 DC fan lock
E8 Input overcurrent detection
F3 Discharge pipe temperature control
F6 High pressure control in cooling
EA Four way valve abnormality
H0 Compressor sensor system abnormality
H6 Position sensor abnormality Compressor start-up failure detected through the position detection circuit. See the H6 page. Full explanation
H9 Outdoor temperature thermistor or related abnormality
J3 Discharge pipe thermistor or related abnormality
J6 Outdoor heat exchanger thermistor or related abnormality
L3 Electrical box temperature rise
L4 Radiation fin temperature rise
L5 Output overcurrent detection
P4 Radiation fin thermistor or related abnormality

Source: Daikin DAMA-SM-23-020, section 4.1 "Error Codes and Description". P4 is displayed only when the system is shut down, per the manual.

Detailed explanations

SafetyThese tables describe what the manufacturer documents say. Gas, combustion, refrigerant and line-voltage repairs are for licensed professionals. If you smell gas, leave the building and call your gas utility or 911. Safety disclaimer.

Sources